50KVA 240V Online UPS 3-1 Ph

Empower heavy-duty manufacturing and large-scale commercial facilities with this 50kVA 3-phase to 1-phase online UPS, engineered for relentless power continuity. Its advanced online double conversion topology utilizes a 32-bit DSP and IGBT-based multi-level conversion to deliver superior electrical resilience. Configured for a 240VDC nominal battery voltage, the system outputs a highly stable 230V pure sine wave supported by a 0.8 power factor. Designed to manage heavy industrial surges, it easily handles a 125% overload for 60 seconds with an absolute 0 msec transfer time. Your critical loads remain completely protected from grid faults by a rugged inbuilt galvanic isolation transformer located at the output. Operating at up to 90% AC-AC efficiency, this 650kg powerhouse features comprehensive fault logging and optional RS 485 connectivity for remote monitoring. Housed in a floor-mounted enclosure, it guarantees a 10+ years design lifespan ideal for textiles, steel plants, and pharma operations.

₹204,895.00 ₹307,343.00

Easy Payment

Free Delivery

Genuine Products

Warranty Assurance

Factory-Direct Delivery

Certified Excellence

Product Overview

The 50KVA 240V Online UPS 3-1 Ph is a three-phase input, single-phase output online UPS from EnerTech’s ETXi series. Its true online double-conversion design with an IGBT rectifier and DSP control delivers a regulated 230 V AC pure sine wave output with zero transfer time, protecting critical loads from every mains disturbance.

Key Features

  • True online double-conversion with advanced IGBT rectifier and inverter
  • DSP-controlled for precise regulation (230 V AC ±1%)
  • Input power factor up to 0.99 with low input THDi (<3%)
  • 0 ms transfer time between mains and battery
  • Overload capacity 125% for 60 s, 150% for 5 s
  • Up to 90% AC-AC system efficiency
  • Parallel redundancy support

Specifications

Rated Capacity50 kVA
Nominal Battery Voltage240 V DC
Phase3-Phase In / 1-Phase Out
Nominal AC Input Voltage Range415V AC (±10%) or 450V AC (3-Phase)
Input Frequency Synchronization Range50 Hz (±10%)
Input Power FactorUp to 0.99 (IGBT Rectifier) / Up to 0.95 (PFC) / Up to 0.8 (SCR)
Nominal AC Output Voltage and Regulation230V AC ± 1% (3:1 Phase) / 415V AC ± 1% (3:3 Phase)
Output Frequency50 Hz ± 0.5%
Output Power Factor0.8
Output Voltage Total Harmonic Distortion (THDv)≤ 3% (100% Linear load), < 5% (100% Non-linear load)
Inverter Overload Capacity125% for 60 s, 150% for 5 s
Transfer Time (Mains to Battery Mode)0 ms (Mains to Battery & Battery to Mains)
Overall System EfficiencyUp to 90% (AC-AC efficiency)
Acoustic Noise Level (at 1 m)≤ 65 dB (Ref: ISO 3746)

Applications